3RR2442-1AA40
CURRENT MONIT. F. IO-LINK S0 SCREW

From SIEMENS

Current monitoring relay for IO-Link, can be mounted to Contactor 3RT2, Size S0 Apparant/active current monitoring 4-40 A, 20-400 Hz, 3-phase Supply voltage 24 V DC 1 change-over contact Monitoring for Current overshoot and undershoot Current asymmetry Phase failure, Cable break Phase sequence, Residual current Blocking current, Switching cycle and Operating hours counter Warning and alarm thresholds Auto-reset or manual reset ON delay 0-9999.9 s OFF delay 0-9999.9 s Reclosing delay 0-300 min Screw connection system
Product brand nameSIRIUS
Product designationMonitoring relays
Design of the productdigitally adjustable, 3-phase current monitoring, IO-Link
Product type designation3RR2
General technical data
Size of contactor can be combined company-specificS0
Operating apparent output rated value2.5 V·A
Insulation voltage
for overvoltage category III according to IEC 60664
— with degree of pollution 3 rated value690 V
Surge voltage resistance rated value6 kV
Protection class IP
on the frontIP20
of the terminalIP20
Shock resistance15g / 11 ms
Mechanical service life (switching cycles)
typical10 000 000
Electrical endurance (switching cycles)
at AC-15 at 230 V typical100 000
Reference code acc. to DIN 40719 extended according to IEC 204-2 acc. to IEC 750K
Reference code acc. to DIN EN 81346-2K
Reference code acc. to DIN EN 61346-2K
Relative repeat accuracy2 %
Supply voltage
Type of voltage of the supply voltageDC
Supply voltage 1 at DC rated value24 V
Relative negative tolerance of the supply voltage25 %
Relative positive tolerance of the supply voltage25 %
Measuring circuit
Type of current for monitoringAC
Adjustable pick-up value current
14 ... 40 A
24 ... 40 A
Adjustable response delay time
when starting0 ... 999.9 s
with lower or upper limit violation0 ... 999.9 s
Adjustable switching hysteresis for measured current value0.1 ... 8 A
Accuracy of digital display+/-1 digit
Precision
Temperature drift per °C0.1 %/°C
Communication/ Protocol
Protocol is supported
IO-Link protocolYes
IO-Link transfer rateCOM2 (38,4 kBaud)
Point-to-point cycle time between master and IO-Link device minimum10 ms
Type of voltage supply via input/output link masterYes
Amount of data
of the address area of the inputs with cyclical transfer total4 byte
of the address area of the outputs with cyclical transfer total2 byte
Auxiliary circuit
Number of CO contacts
for auxiliary contacts1
Operating current of auxiliary contacts at AC-15
at 24 V3 A
at 230 V3 A
Operating current of auxiliary contacts at DC-13
at 24 V1 A
at 125 V0.2 A
at 250 V0.1 A
Contact rating of auxiliary contacts according to ULB300 / R300
Main circuit
Operating power
rated value2.5 W
Outputs
Operating current at 17 V minimum5 mA
Electromagnetic compatibility
EMC emitted interference
acc. to IEC 60947-1ambience A (industrial sector)
EMI immunity
acc. to IEC 60947-1ambience A (industrial sector)
Safety related data
Protection against electrical shockfinger-safe
Connections/Terminals
Product function
removable terminal for main circuitNo
removable terminal for auxiliary and control circuitYes
Type of electrical connection
for main current circuitscrew-type terminals
for auxiliary and control current circuitscrew-type terminals
Type of connectable conductor cross-sections
for main contacts
— solid2x (1 ... 2.5 mm²), 2x (2.5 ... 10 mm²)
— finely stranded with core end processing2x (1 ... 2.5 mm²), 2x (2.5 ... 6 mm²), 1x 10 mm²
at AWG conductors for main contacts2 x (16 ... 14), 2x (14 ... 8)
Connectable conductor cross-section for main contacts
single or multi-stranded1 ... 10 mm²
finely stranded with core end processing2.5 ... 10 mm²
Type of connectable conductor cross-sections
for auxiliary contacts
— solid1x (0.5 ... 4 mm²), 2x (0.5 ... 2.5 mm²)
— finely stranded with core end processing1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²)
at AWG conductors for auxiliary contacts2x (20 ... 14)
AWG number as coded connectable conductor cross section
for main contacts16 ... 8
Tightening torque
with screw-type terminals0.8 ... 1.2 N·m
Installation/ mounting/ dimensions
Mounting positionany
Mounting typedirect mounting
Height87 mm
Width45 mm
Depth91 mm
Required spacing
with side-by-side mounting
— forwards0 mm
— Backwards0 mm
— upwards0 mm
— downwards0 mm
— at the side0 mm
for grounded parts
— forwards6 mm
— Backwards0 mm
— upwards6 mm
— at the side6 mm
— downwards6 mm
for live parts
— forwards6 mm
— Backwards0 mm
— upwards6 mm
— downwards6 mm
— at the side6 mm
Ambient conditions
Installation altitude at height above sea level
maximum2 000 m
Ambient temperature
during operation-25 ... +60 °C
during storage-40 ... +80 °C